: [email protected] Appendix A.8.6. Setting the Priority of Intrinsic Alarming
Priority for off normal events
Priority for normal events
A BACnet EventNotification message contains a Priority field indicating the priority of the event being reported. The Priority values to be used are configured via the
Priority property of the Notification Class object, using the configuration file parameters Pri_to_offnormal, Pri_to_normal and Pri_to_fault, which determine the priorities
to be used respectively for all to-offnormal, to-normal and to-fault transitions reported via the Notification Class object.
Priority Values should be chosen as follows:
Critical Equipment Message