: [email protected]m 5.3.2 Driver Related Map Descriptor Parameters
Name of Node to fetch data from
One of the node names
specified in “Client Node
Descriptor” above
Specifies the command that will be sent to the
eLumen.
Area Machine:
Run_Script_AB
Area_Sts_Offscene
Sel_Scene_In_Area
Run_Script_Multi
Area_Status
Scene_In_Area_Status
Sys_Var_Val_Bin
Sys_Var_Val
Zone Machine:
Run_Script_Ab
Zone_Intensity
Fade_Zone
Run_Script_Multi
Zone_Intensity
Sys_Var_Val_Bin
Sys_Var_Val
Name of Data Array that contains a list of parameters
needed to execute the command.
The offset into the DA_Lut_List Data Array from
where the list data is to be used.
0 to the maximum offset into
the DA_Lut_List Data Array.
Name of Data Array that contains parameters
needed to execute the command.
The offset into the DA_Lut_Parms Data Array where
the driver will retrieve the parameters.
0 to the maximum offset into
the DA_Lut_Parms Data Array.
GRAFIK system area number
GRAFIK system variable number
GRAFIK system zone number
Length of Map Descriptor. The length is an indication
of the number of data elements this Map Descriptor
is responsible for updating. It is used in the overall
points calculation of the FieldServer.
See example Map Descriptors
for individual lengths per Map
Descriptor.
The length of the Data Array specified under
DA_Lut_List when used with Grafik command:
run_script_multi
5.3.3 Timing Parameters